Outdoor-rated cord with the gauge, length and plugs your load needs.
Enter the load and length to see the gauge you need.
What gauge cord do you need from the generator to your appliances? Enter the load and the length. Results update as you type.
The minimum wire gauge, the voltage drop for each gauge, and the outlet and plug the load needs.
Current runs from the generator to the appliance and back, and the copper in the cord resists it. The longer and thinner the cord, the more voltage is lost on the way. Too much loss makes motors run hot and appliances misbehave.
The cord's marked amp rating and both plugs must cover the load as well. Lower gauge numbers are thicker wire. Feeding home circuits needs a transfer switch or interlock fitted by a licensed electrician, never a cord into a wall outlet.
A 1,500 W space heater on a 100 ft cord, allowing 5% voltage drop:
12.5 A is above the 12 A continuous limit of a 15 A plug, so the cord and outlet need to be 20 A rated. At the stricter 3% limit, the answer is 10 AWG.
It depends on the current and the length. For a 1,500 W load at 120 V (12.5 A) over 100 ft, 12 AWG keeps the voltage drop near 4%. Lower gauge numbers are thicker wire. Longer runs and heavier loads need thicker cord.
Current flows out and back along the cord, and the copper resists it, so the voltage at the far end drops. Too much drop makes motors run hot and can stop appliances working. A thicker wire has less resistance.
For small loads, yes, if it is rated for outdoor use and its amp rating covers the load. Most household cords have 15 A plugs and thin 16 AWG wire, which is fine for a fridge but not for a space heater 100 ft away.
No. Backfeeding through an outlet can electrocute utility workers and neighbors, and can start a fire. To power home circuits, have a licensed electrician fit a transfer switch or an interlock and an inlet box.
What to look for. Sizes appear once the calculator has a result.
We may earn a commission from links on this page. How this works
Outdoor-rated cord with the gauge, length and plugs your load needs.
Enter the load and length to see the gauge you need.
The safe way to feed home circuits, with a transfer switch or interlock. Fitted by a licensed electrician.
For feeding home circuits through a transfer switch, fitted by an electrician.